Vadodara, Gujarat, India
info@aquasafemine.com

ASM’s Brackish Water Reverse Osmosis (BWRO) plants are designed to treat ground/surface or industrial water with <5,000 mg/L of dissolved solids (TDS) and <30 mg/L of suspended solids (TSS), to achieve potable water quality. The standard treatment process involves pre filtration (auto-backwashing multimedia filters and cartridge filters), anti-scalant dosing to prevent membrane scaling, RO desalination and a CIP system for membrane cleaning.

Additional pre-RO and post-RO treatment steps may be added as required to suit feed water conditions and/or treated water quality requirements. The BWRO plants are available as skid mounted or containerised systems.

If you have specific requirements, contact us to discuss our custom designed desalination plants or ask about our hire options.

STANDARD SPECIFICATIONS

Parameter Units BWRO-50 BWRO-100 BWRO-150 BWRO-250 BWRO-500 BWRO-1000
Permeate Flow Rate m3/day 50 100 150 250 500 1000
Permeate Recovery Rate % 60~85 (varies according to feed water quality and RO configuration)
Permeate TDS mg/L <500 (typical)
Raw Water TDS mg/L <5000
Raw Water TSS mg/L <30
Raw Water Temperature °C 15 ~ 35
Ambient Design Temperature °C 5 ~ 45 (-15 ~ 50 for insulated containerised system)
Feed Water Inlet Pressure kPa >15 (flooded suction)
Permeate Discharge Pressure kPa ~40 (higher discharge pressures available on request)
Brine Discharge Pressure kPa ~40 (higher discharge pressures available on request)
Power Supply AC 380~450 V, 3 Phase, 50/60 Hz
Power Consumption kW 4.1 7.7 10.5 15 29.5 52
No. Containers (Optional) 1 x 20’ 1 x 20’ 1 x 40’ 1 x 40’ 2 x 40’ 2 x 40’

STANDARD INCLUSIONS + OPTIONS

✓= Standard Supply o = Optional Supply – = Not Applicable

Equipment BWRO-50 BWRO-100 BWRO-150 BWRO-250 BWRO-500 BWRO-1000
Skid Mounted Plant & Equipment
Low Pressure Feed Pump
High Pressure RO Pump
Pre-filtration Multimedia o
Ultra Filtration o o o o o o
Cartridge Filters
Anti Scalant Dosing System
Membrane CIP System
PLC Control System with HMI
Containerised system, c/w A/C & Lights o o o o o o
Container Insulation (walls & ceiling) o o o o o o
Container non-slip floor coverings o o o o o o
Container Side Access Door o o
Additional Pre-RO Treatment o o o o o o
Additional Post-RO Treatment o o o o o o
Premium Instrumentation Package o o o o o

 

Instrumentation Standard Package Premium Package
Pressure Gauges
Pressure Transmitters (4-20 mA)
HP RO Pump Inlet Low Pressure Switch
Flow Gauges (Rotameters)
Flow Transmitters (4-20 mA)
Conductivity Transmitter (4-20 mA)
Float Switches (Feed/Permeate, Chemical Dosing & CIP Tanks)
Remote Monitoring & Control Capabilities
How can we help you?